| [Home] | |
| |
|
By M. Nadeem
Ener Save Consultants Pvt. Ltd.
New Delhi
Nadeem is a M. Tech from IIT Delhi and works as a consulting engineer with Ener Save whose head office is in Canada. He has been involved in the design of some innovative projects in India such as Geothermal Heat Pumps and Solar Run air conditioning system, for the past 10 years.
A water chilling machine is the most important component of a central airconditioning system. There are several types of chillers available viz reciprocating, rotary screw, centrifugal, centrifugal with VSD etc. All these chillers behave differently at varying operating conditions (cooling load and coincident cooling fluid temperatures), which are application specific. Thus, for determining the most efficient type of chiller for a particular application, the year round performance, and not just the performance at the design conditions, needs to be evaluated. The criteria as laid down by ARI - Standard 550/590 (1998) for determining the overall performance of chillers is generalized, and as a result can only predict nonapplication specific performance behavior. See Table 1 and Figure 1.

Most often, the flow through the condenser and evaporator of a chiller are kept constant. Thus, condenser cooling fluid temperature and part loads become the primary parameters for determining the performance of the chiller. See Figure 2. These two parameters are application specific and are variable round the year. Moreover, different types of chillers behave differently under these two variable parameters. Under the same operating conditions one particular type may be more efficient than another type but the reverse may be true for the same chillers under some other operating conditions.

[top]
At any time, a chiller can operate at the following two different operating conditions:
| Table1 : Part Load Conditions for Rating as per ARI Standard 550/590(1998) | ||
|---|---|---|
| IPLV | NPLV | |
| Evaporator (All Types) 100% Load LWT 0% Load LWT Flow Rate (gpm) Field fouling allowance (F.F.A.) |
44°F [6.7°C] 44°F [6.7°C] 2.4 gpm/ton [0.043 L/s per kW] 0.0001 |
Selected LWT Same as 100% load Selected gpm/ton [L/s per kW] As specified |
| Condenser (Water
Cooled) 100% load EWT 75% load EWT 50% load EWT 25% load EWT 0% load EWT Flow rate (gpm) [L/s] F.F.A. |
85°F [29.4°C] 75°F [23.9°C] 65°F [18.3°C] 65°F [18.3°C] 65°F [18.3°C] 3.0 gpm/ton [0.054L/s per kW] 0.00025 |
Selected EWT 65°F (18.3°C)} 65°F (18.3°C) 65°F [18.3°C] Selected gpm/ton [L/s per kW] As specified |
|
Assumptions:
Note: The intent of part load ratings in terms of IPLV and NPLV is to permit the development of part load performance over a range of operating conditions. NPLV instead of IPLV is used to develop application part load performance at conditions other than ARI standard rating conditions. |
||
For COP and EER
IPLV or NPLV = 0.01A + 0.42B + 0.45C + 0.12D
where:
A = COP or EER at 100%
B = COP or EER at 75%
C = COP or EER at 50%
D = COP or EER at 25%
For kW/Ton
IPLV or NPLV = 1 / {(0.01/A) + (0.42/B) + (0.45/C) + (0.12/D)}
Where:
A = kW/Ton at 100%
B = kW/Ton at 75%
C = kW/Ton at 50%
D = kW/Ton at 25%
The prevalent criteria for the performance evaluation of chillers, as laid down by ARI has the following limitations:

Click to view the clear picture
[top]
Due to the above assumptions, criteria laid down by ARI for the performance evaluation of chillers can only give non-application specific results.
Thus, for determining the type of chiller which will be most efficient for
a particular application, year round evaluation of the following two parameters
needs to be done:
Year round hourly cooling load variation.
Determination of condenser cooling fluid (water or air) temperature coincident
with each cooling load value.

An existing prestigious five star hotel located in New Delhi had their centrifugal chillers installed in 1978. These chillers were selected with R- 11 as refrigerant and had already served their useful life, as a result had high operation and maintenance cost. Our firm was asked to suggest a suitable replacement for the chillers. Since, as energy audit consultants for the same hotel, we already had detailed cooling load patterns for various areas, we undertook the exercise of year round performance evaluation for various types of chiller options considered and made our recommendation accordingly.
The hotel comprises of approximately 30,000m2 of covered area on eight floors. There are a total of 296 guest rooms in the hotel apart from restaurants, banquet halls, shops, lobby etc. In addition, there is a separate arrangement to provide conditioned fresh air to guest rooms for ventilation.
The hotel has the following features, which are typically true for large hotels in India:
The peak block cooling load for the existing hotel is 800 tons and it has two working chillers of 400 tons each (centrifugal water cooled type). The year round cooling load variations along with coincident cooling fluid temperatures were analyzed and evaluated (for 8760 hours) using the following procedure:

Click to view the clear picture
[top]
Using the above procedure, the hourly net block cooling loads were evaluated for 8760 hours (365 x 24). The performance of each chiller type was worked out based on the following procedure:
None of the chillers operated when there was no cooling load requirement i.e. during winters, taking into account the effect of ambient conditions, internal and external heat transfer etc.
For each chiller type, considering flow rate through condenser and evaporator as constant, the efficiency dependence in terms of Entering Cooling Water Temperature (ECWT) and part load is known from various manufacturers. Thus, at each value of block cooling load (hence, part load on the chiller) and coincident cooling fluid temperatures, hourly power consumption for each chiller type was obtained from the manufacturers. Typical part load power consumption at various entering cooling water temperatures for 400 ton Centrifugal, Rotary Screw and Centrifugal Chiller with VSD are as shown in Tables 2, 3 & 4. At each hour, block cooling load and hence, part load on each chiller is evaluated while simultaneously obtaining coincident cooling fluid temperatures from the hourly weather data. This combined information is utilized to determine hourly specific power (kW/Ton) and hence the total power consumption for each chiller type from the available part load performance characteristics (refer Power Consumption Tables 2, 3 & 4).
| Table 2 : Power Consumption kW/ton (Centrifugal Chillers) % Loading |
|||||||
|---|---|---|---|---|---|---|---|
| ECWT | 100% | 87.50% | 75% | 62.50% | 50% | 37.50% | 25% |
| 90 DEG F 86 DEG F 82 DEG F 78 DEG F 74 DEG F 70 DEG F 66 DEG F |
0.625 0.605 0.571 0.539 0.511 0.484 0.459 |
0.633 0.597 0.565 0.536 0.510 0.485 0.462 |
0.635 0.601 0.571 0.544 0.519 0.494 0.470 |
0.652 0.618 0.588 0.561 0.536 0.510 0.484 |
0.686 0.652 0.621 0.593 0.566 0.539 0.512 |
0.750 0.714 0.681 0.652 0.623 0.595 0.567 |
0.950 0.835 0.803 0.775 0.748 0.724 0.700 |
| Table 3 : Power Consumption kW/ton (Rotary Screw Chillers) % Loading |
|||||||
|---|---|---|---|---|---|---|---|
| ECWT | 100% | 87.50% | 75% | 62.50% | 50% | 37.50% | 25% |
| 90 DEG F 86 DEG F 82 DEG F 78 DEG F 74 DEG F 70 DEG F 66 DEG F |
0.627 0.585 0.543 0.500 0.475 0.458 0.440 |
0.629 0.589 0.552 0.520 0.497 0.468 0.434 |
0.663 0.617 0.570 0.527 0.487 0.447 0.413 |
0.687 0.635 0.587 0.544 0.496 0.448 0.417 |
0.780 0.720 0.660 0.595 0.530 0.475 0.445 |
0.941 0.862 0.783 0.697 0.625 0.559 0.513 |
1.310 1.190 1.080 0.960 0.840 0.750 0.670 |
| Table 4 : Power Consumption kW/ton (Centrifugal Chillers
with VSD) % Loading |
|||||||
|---|---|---|---|---|---|---|---|
| ECWT | 100% | 87.50% | 75% | 62.50% | 50% | 37.50% | 25% |
| 90 DEG F 86 DEG F 82 DEG F 78 DEG F 74 DEG F 70 DEG F 66 DEG F |
0.652 0.598 0.547 0.499 0.452 0.408 0.370 |
0.634 0.578 0.527 0.479 0.433 0.388 0.347 |
0.630 0.572 0.518 0.467 0.420 0.376 0.333 |
0.644 0.587 0.543 0.466 0.415 0.366 0.322 |
0.682 0.610 0.557 0.497 0.439 0.365 0.318 |
0.782 0.679 0.598 0.528 0.463 0.400 0.341 |
0.912 0.846 0.719 0.621 0.531 0.452 0.382 |
|
[top]
The specific and annual power consumption for different types of chillers viz rotary screw, centrifugal and centrifugal with VSD were worked out using the procedure as described above and ARI standard 550/590 (1998)
| Type of Chiller | **IkW / ton | Total Energy Consumption per Annum (kWh) |
| Rotary Screw Chiller Centrifugal Centrifugal with VSD |
0.603 0.589 0.516 |
1,093,634 1,067,853 935,852 |
| Type of Chiller | **IkW / ton | Total Energy Consumption per Annum (kWh) | Variation w.r.t. hourly simulation procedure |
| Rotary Screw Chiller Centrifugal Centrifugal with VSD |
0.499 0.544 0.378 |
904,962 986,177 685,610 |
17.25% 7.65% 26.74% |


[top]
|
Based on the above case study for the hotel, it is concluded that overall performance characteristics of different types of chillers differ significantly than as predicted by ARI standard 550/590 (1998). See Figure 6 and 7. This difference is primarily owing to higher cooling fluid temperatures at lower part loads and vice versa. Moreover, it is also inferred that, generally, screw chillers are less efficient than normal centrifugal chillers at part loads when the cooling fluid temperatures are higher. Also, at any given cooling fluid temperature, all positive displacement type of chillers are less efficient at part load than at full load, see Figure 2. However, non positive displacement type of chillers have their best efficiencies at approximately 80% part load.
[top]